    What Is a Low Voltage Electrical Switchboard and How Does It Work?

    A component-by-component technical guide to LV switchboard function, construction, IEC 61439-1 compliance requirements, and industrial applications across Saudi Arabia.

    EAMFCO LV Switchboards

    IEC 61439-1 compliant low voltage switchboards rated up to 6,300A custom-engineered for Saudi industrial, data centre, and infrastructure projects.

    Need a switchboard specification?

    Our engineers provide SLD review, load calculations, and full documentation for Saudi project tenders and SEC approval submissions.

    Definition

    A low voltage switchboard is a free-standing electrical assembly that receives incoming power from a transformer or utility supply at voltages up to 1,000V AC, and distributes it to outgoing circuits through protective devices including circuit breakers, fuses, and contactors. It forms the primary power distribution point of an industrial or commercial electrical installation, housing metering, protection, and control equipment within a single rated enclosure.

    The Role of a Switchboard in Industrial Power Distribution

    In an industrial or large commercial facility, electrical power arrives from the utility network or an on-site generator at medium voltage (MV) typically 13.8 kV or 33 kV in Saudi Arabia. A transformer steps this down to low voltage (400V three-phase at 50 Hz). The transformer secondary connects via busduct or cable to the main LV switchboard, which performs four functions simultaneously:

    01

    Incoming Protection

    The main circuit breaker or switch-disconnector isolates the entire LV installation from the transformer on fault or for maintenance the single point of isolation for the complete facility.

    02

    Load Distribution

    Outgoing feeder breakers distribute power to sub-distribution boards, motor control centres, and large individual loads controlling current path and capacity for each circuit.

    03

    Fault Discrimination

    Selective trip coordination between the main breaker and outgoing feeders ensures a downstream fault trips only the affected feeder, not the entire facility supply.

    04

    Measurement & Monitoring

    Metering instruments record kWh, kVAR, power factor, voltage, and maximum demand inputs to SEC billing, facility energy management, and SCADA systems.

    EAMFCO's low voltage switchboards handle the full scope of main electrical distribution from the Main Distribution Board (MDB) at the transformer secondary through to Sub-Main Distribution Boards (SMDB) serving individual building zones or process areas.

    Key Components of a Low Voltage Switchboard

    Main Incoming Breaker (ACB)

    up to 6,300A
    The Air Circuit Breaker (ACB) is the primary protective and switching device on the incomer. It provides overload, short circuit, and earth fault protection for the entire downstream installation. Modern ACBs incorporate electronic trip units with adjustable long-time, short-time, and instantaneous settings allowing precise coordination with downstream MCCBs. Ratings for EAMFCO switchboards extend to 6,300A continuous.

    Main Busbar Assembly

    99.99% tinned copper
    The horizontal and vertical busbars form the backbone of the switchboard distributing current from the incomer to all outgoing functional units. EAMFCO switchboards use 99.99% purity tinned copper busbars, which offer superior conductivity, corrosion resistance, and contact reliability compared to untreated copper or aluminium alternatives. Busbar cross-section is sized for rated current with allowance for the maximum ambient temperature at the installation site.

    Outgoing Feeder MCCBs / ACBs

    Form 3 / Form 4B
    Moulded Case Circuit Breakers (MCCBs) protect individual outgoing circuits from overload and short circuit. Each MCCB is rated for the specific circuit it protects motor feeders, sub-distribution boards, UPS inputs, and lighting circuits all have different characteristics requiring different trip curve selections (B, C, D curves for MCCBs; LSI settings for ACBs). Segregation level (Form 3 or 4B) determines whether adjacent functional units are individually enclosed.

    Metering & Instrumentation

    Revenue / check meter
    Switchboards for SEC-connected facilities include current transformers (CTs) for metering and protection on the incomer. Instruments typically installed: digital multifunction meter (kWh, kVAR, power factor, voltage, current, frequency, maximum demand), ammeter per phase, voltmeter with selector switch, and power factor meter. For SEC revenue metering, the CT ratio and meter class must comply with SEC metering specifications.

    Neutral & Earth Busbars

    TN-S / TN-C-S
    Separate neutral and protective earth (PE) busbars required for TN-S earthing systems used in Saudi projects per IEC 60364 and SEC standards. The neutral busbar carries return current; the PE busbar provides the fault current return path. They are connected at one point only (the main earthing terminal) to prevent circulating currents and to ensure correct RCD operation.

    Enclosure & Segregation

    IP43 / IP55 / IP65
    The steel sheet enclosure provides mechanical protection and IP-rated ingress protection. Internal segregation (Form 1 through Form 4B per IEC 61439-1) defines the degree of separation between busbars, functional units, and cable termination compartments. Form 4B is specified for critical installations where maintenance access to one functional unit must not expose live components in adjacent units.

    How a Switchboard Differs from a Panelboard

    The terms are often used interchangeably in the field, but they describe different equipment with different ratings, construction, and applications. Understanding the distinction matters when specifying distribution equipment for Saudi projects:

    ParameterLV SwitchboardPanelboard / Distribution Board
    Rated current400A to 6,300ATypically ≤ 400A (IEC) or ≤ 1,200A (NEC)
    Physical sizeFree-standing, floor-mounted multi-sectionWall-mounted or recessed compact single enclosure
    ConstructionModular, draw-out or fixed functional units, large busbarFixed components, smaller busbar, limited modularity
    Incoming deviceAir Circuit Breaker (ACB) adjustable trip unitMCCB or main switch fixed or adjustable
    Segregation levelForm 2 to Form 4B per IEC 61439Typically Form 1 no internal segregation
    ApplicationMain Distribution Board (MDB), primary power distributionSub-distribution, final circuits, tenant distribution
    MeteringFull revenue/check metering as standardSub-metering only not revenue grade
    MaintenanceLive maintenance possible (Form 4B) with isolation of individual unitsFull de-energisation required for most work
    Position in hierarchyNearest to transformer secondary highest in distribution hierarchyDownstream of MDB or SMDB serves final loads

    In EAMFCO's distribution hierarchy for Saudi projects: the transformer secondary feeds the Main Distribution Board (MDB) - a switchboard. The MDB feeds Sub-Main Distribution Boards (SMDBs) - which may be switchboards or large panelboards. SMDBs then feed Final Distribution Boards (FDBs) - panelboards serving individual floors, zones, or process areas.

    IEC Compliance Standards for Low Voltage Switchboards

    IEC 61439-1 is the overarching standard for all low voltage switchgear and controlgear assemblies. It defines verification requirements that the manufacturer must meet for the complete assembly not just individual components. For Saudi Arabia, compliance with IEC 61439-1 and its sub-parts is mandatory on all projects procured by SEC, Saudi Aramco, NWC, and public sector infrastructure programmes.

    StandardScope
    IEC 61439-1General rules definitions, electrical characteristics, temperature rise limits, dielectric properties, short circuit withstand, mechanical operation, degree of protection
    IEC 61439-2Specific requirements for power switchgear and controlgear assemblies (PSC-assemblies) applies directly to LV switchboards
    IEC 60947-2Low voltage circuit breakers the standard governing ACBs and MCCBs installed in the switchboard
    IEC 60529IP degree of protection classification referenced for enclosure specification
    IEC 60364Electrical installations of buildings defines earthing system (TN-S, TT) requirements that the switchboard neutral and earth arrangements must match
    SASOSaudi Standards, Metrology and Quality Organization mandatory certification for electrical equipment installed in Saudi Arabia

    Verification under IEC 61439-1 covers temperature rise (confirmed by test or calculation), short circuit withstand (confirmed by test or comparison with type-tested reference design), dielectric strength, mechanical endurance, and IP rating. EAMFCO LV switchboards are designed in accordance with IEC 61439-1 with segregation available up to Form 4B and IP ratings to IP65.

    Where LV Switchboards Are Used in Saudi Arabia

    Data Centres

    Hyperscale and colocation data centres require switchboards with highest reliability: Form 4B segregation, dual bus arrangements with bus-coupler ACBs, and fast fault discrimination. EAMFCO supplied LV switchgear and switchboards for Shovelnose, Stingray, Edgnex, and STC data centres in Saudi Arabia.

    Industrial Plants

    Petrochemical, manufacturing, food processing, and fabrication facilities use switchboards as main distribution points, stepping down transformer output to MCCs, sub-boards, and large motors. Ratings of 2,500–6,300A are common for plants with 2–5 MVA transformer banks.

    Commercial Buildings & Hotels

    High-rise towers, hotels, and shopping malls use switchboards as building main distribution boards, with section boards per floor or zone. EAMFCO supplied LV switchgear for Al Salam Hotel and Taazeez Tower projects.

    Water & Infrastructure

    Pump stations, desalination facilities, and water treatment plants use switchboards rated for continuous heavy motor loads with high short circuit levels from stiff utility supplies.

    Frequently Asked Questions

    Q: What is the rated current of a low voltage switchboard?

    A: LV switchboards range from 400A for small commercial installations to 6,300A for large industrial main distribution boards. The rated current corresponds to the busbar continuous current rating and is determined by maximum demand load plus a growth contingency. EAMFCO manufactures LV switchboards up to 6,300A per IEC 61439-1.

    Q: What is the difference between Form 1, Form 2, Form 3, and Form 4 segregation?

    A: IEC 61439 segregation forms define internal separation between busbars, functional units, and terminal compartments. Form 1 has no segregation. Form 2 separates busbars from functional units. Form 3 additionally separates functional units from each other. Form 4B provides the highest level all units and terminals individually enclosed allowing maintenance on one unit without exposing adjacent live components. Form 4B is standard for data centres, hospitals, and critical process plants in Saudi Arabia.

    Q: What IP rating should a switchboard have for a Saudi industrial installation?

    A: Indoor, air-conditioned electrical rooms: IP41 or IP43 minimum. Dusty industrial environments fabrication yards, cement, petrochemical: IP54. Outdoor or sand-exposed installations: IP55 or IP65. EAMFCO LV switchboards are available in IP43, IP55, and IP65 configurations.

    Q: What does IEC 61439-1 compliance mean for a switchboard?

    A: IEC 61439-1 defines verification requirements for the complete assembly temperature rise limits, dielectric strength, short circuit withstand, mechanical operation, and degree of protection. Compliance may be verified by type testing or by design calculation. For projects procured by Saudi Aramco, NWC, or SEC, IEC 61439-1 compliance is a mandatory contractual requirement.

    EAMFCO - IEC 61439-1 Compliant LV Switchboards for Saudi Projects

    EAMFCO manufactures custom-engineered low voltage switchboards rated up to 6,300A with Form 4B segregation, IP65 protection, and full factory testing for industrial plants, data centres, hospitals, and infrastructure projects across Saudi Arabia. Continue reading:

    ABOUT COMPANY

    EAMFCO LogoEAMFCO
    Saudi Made Logo

    CONTACT INFO

    You can always contact us via email or phone. Get in touch with contact and get a quote form.

    Second Industrial City, Dammam, Saudi Arabia
    920010487
    info@eamfco.com

    COMPANY SUPPORT

    KSA Map

    Our support team is available during business hours.

    Sunday-Thursday: 7am to 5pm
    Friday & Saturday: Closed

    We deliver across the Kingdom.